Skip to content

OPC UA PLC simulator

Test your HMI before the PLC is available

Expose any running session as an OPC UA endpoint and connect your HMI or SCADA client to it. The logic keeps scanning on our servers, so screens, alarms and trends respond to running logic instead of static test values.

Run an exampleBrowse examples
OPC UAHMISCADALive tags

A running session becomes an opc.tcp:// endpoint your client can browse

  1. 01 Run
  2. 02 Expose
  3. 03 Connect your client
SLOT 1 · LIVE   Filler_Line_2 v4
OPC UA  opc.tcp://<your-endpoint>:4841
A slot with an exposed endpoint
The Session access dialog in PLCflow Sim after a running session is exposed: an opc.tcp:// endpoint address, the username plcsim, and a hidden password with Show and Copy buttons.
A session just after Expose. The address, username and password are what your client needs.

What your HMI or SCADA client gets

An endpoint it can browse

Your client browses and reads the session's tags over OPC UA. Each exposure has its own password.

Reads and writes

Your HMI reads live values and writes back into the running logic, aliases included.

Stays up when you close the tab

Sessions scan on our servers, so the endpoint stays up after you close the tab.

Exposed only when you say so

Nothing is exposed until you expose it. How long an endpoint stays up is set by your plan and shown in the app.

With and without a simulator

Without a simulator

  1. HMI screens tested against static tags or a borrowed controller
  2. Alarm logic first exercised on site

With PLCflow Sim

  1. Screens bound to a running program before the hardware arrives
  2. Alarms fire because the logic fired them

Who uses it this way

HMI developer

Builds screens in parallel with the PLC programmer, against the program as it stands.

SCADA integrator

Tests tag mapping before there is site access.

Trainer

Runs an HMI lab with no hardware on the bench.

Testing HMI and SCADA without a PLC

Try it on an example

Pump station (L5X)

L5X import

An L5X program export with lead/lag pumps, program-scope tags and a JSR'd alarm routine.

TankLevelLeadPumpLagPump

Tank level alarms

Structured Text

Level alarms with hysteresis, in Structured Text. Each alarm sets at one level and clears at another.

LevelHighAlarmFillValve

OPC UA endpoint questions

How long does an OPC UA endpoint stay up?

It depends on the plan: 25 minutes on Free (the length of the free session), 7 days on Standard, 30 days on Pro, and no time limit on Integrator. Endpoints at a time: 1 on Free, 1 on Standard, 3 on Pro, 5 on Integrator.

Is the endpoint protected?

Yes. Each exposure gets its own password, and the connection is signed and encrypted. Stopping the exposure and exposing again gives a fresh password.

Can I use the endpoint to control real equipment?

No. It is for test clients only.

Safety & Responsible Use

See it run

Open an example and press Run. It needs no install and no account.

Run an example