Skip to content

HMI and SCADA testing

Test HMI and SCADA screens against running logic

The HMI team usually waits for the PLC. Run the program in PLCflow Sim instead, expose the session over OPC UA and connect your HMI. Control it as you would with a PLC – screens, alarms and trends respond to the logic as it scans.

Run an exampleHow the OPC UA endpoint works

The situations

Screens before the panel is built

The situation. The PLC program exists, or most of it does. The hardware doesn't.

What you do. Run the program, expose it, and bind your screens to its tags now, under the names they have in the program.

Alarms

The situation. Alarm setpoints and messages usually get their first real test on site.

What you do. Change the level, pressure or fault tag from the tag list and watch the alarm raise and clear on your screen, with the deadband the logic gives it.

Operator training and demos

The situation. An operator session or a client demo, and no hardware on the bench.

What you do. Run the program in a slot, connect the HMI, and let people operate it. What they write from the screen lands in the running logic.

How to set up

  1. Run your program in a live slot.
  2. Expose the session. You get an opc.tcp:// address, a username and a password for that exposure.
  3. In your client, add an OPC UA connection to that address with that username and password. Trust the server's certificate when asked.
  4. Browse the tags and bind them.

The app has a step-by-step guide for Ignition 8.1. Other OPC UA clients need the same three things: the address, that security mode, and the username and password.

The Session access dialog in PLCflow Sim after a running session is exposed: an opc.tcp:// endpoint address, the username plcsim, and a hidden password with Show and Copy buttons.
Step 2: the session's endpoint, ready for your client. The password stays hidden until you show or copy it.
Try it out

What it can't tell you

Your screens are talking to simulated logic. Communication timing, your controller's own driver, I/O faults and device behaviour are not modelled, and the path to each tag is PLCflow Sim's, so expect to set the connection up again on site. An endpoint is for test clients only. Never connect it to anything that drives real equipment.

Safety & Responsible Use

Which plan fits

It comes down to how long an endpoint has to stay up.

FreeStandardProIntegrator
Endpoints at once1135
Each stays up25 minutes (the session)7 days30 daysno time limit

Those are the longest an endpoint can stay up. Separately, an endpoint nobody has touched for 30 days is withdrawn, Integrator's included. You can expose the session again when you need it.

PLC simulator pricing

Examples to try

Tank level alarms

Structured Text

Level alarms with hysteresis, in Structured Text. Each alarm sets at one level and clears at another.

LevelHighAlarmFillValve

Pump station (L5X)

L5X import

An L5X program export with lead/lag pumps, program-scope tags and a JSR'd alarm routine.

TankLevelLeadPumpLagPump

HMI and SCADA testing questions

Which HMI and SCADA software works?

Any OPC UA client that supports Basic256Sha256 / SignAndEncrypt with a username and password should connect. The in-app guide covers Ignition 8.1 step by step. If another client gives you trouble, let us know through the contact form.

Contact us

Do my tag names stay the same?

Yes. The endpoint publishes the tags under the names they have in your program, aliases included. The path to them is PLCflow Sim's own, so the connection settings will differ from your controller's.

How is the endpoint protected?

Each exposure gets its own password, and the connection is signed and encrypted. Stopping the exposure and exposing again gives a fresh password.

Start with an example

Open one and press Run. You don't need an account.

Run an example